The differential current relays type SKC is intended for the protection of generators, large motors, two winding power transformers and short lines.
The relay SKC feature the following characteristics:
- seven current inputs, where six are provided for current phase measurements and the last one dedicated for residual current measurement;
- internal compensation of phase shift and ratio matching for transformers differential function (87T); conventional external compensation can also be selected with external CT's;
- stabilizing circuit with dual slope with variable bias makes the differential functions of SKC relay insensitive to external fault (87T, 87G);
- second and fifth harmonic restraint stabilization with strong magnetizing inrush currents and overexitation condition (87T) based on numerical processing of differential current (DFT algorithm);
- alernative set thresholds for 49-50-51-50N-51N/87N protection functions which are automatically enabled upon detection of high second harmonic above a programmable set-point to prevent tripping for transformer energization (inrush);
- earth fault protection insensitive to thirth and higher harmonic components;
- selectable operation curves with independent or dependent time (first thresholds) for overcurrent and earth fault functions;
- trip counting performed for each function;
- shorting values of input quantities corresponding to the four last operations (START or TRIP) and trace memory with pre and post trigger;
- four final relays, independently programmable as energized/de-energized and latched/no-latched;
- three signalling LEDs (ON,TRIP,ALARM);
- two digital inputs circuits;
- double set-point groups (bank A and bank B)
- blocking circuits to perform accelerated protection schemes either with programmable logic from internal funtions with block circuits of external protection relays;
- trip circuit supervision (TCS)
- breaker failure protection (BF)
- serial communication circuit RS485 with MODBUS RTU protocol;
- real time clock with memory backup;
- continuous monitoring of internal circuits ;(SELF TEST).

Specifications
Key:
standard
optional
alternative
Applications
- Transformer
Protection functions
- Thermal image (49)
- Phase overcurrent (50/51)
- Residual overcurrent (50N/51N)
- Differential protection for generators and motors (87G/87M)
- High impedance restricted earth fault (87NHIZ)
- Biased differential for transformer (87T)
- Breaker failure (BF)